Light Weight Cement Specification
 
sheet style
Light Weight Cement in filled Steel Floor slabs made of Cold roll Steel forming covered around all sides, coated outside and inside with Epoxy Powder Coating to prevent rust, inside packed with Light Weight Cementitious material to increase load-bearing capacity. Impact Load & Rolling Load, and as a result, the size remains unchanged.
 
Sheet size
600x 600 x 35 mm.
 
surface material
High Pressure Laminated ( HPL-Floor grade, Anti Static, Bare ), raised floor height: standard 10 - 60 centimeters or more than 60 centimeters
lifting weight of the floor
 
test standard
CISCA Standard (Matterial Test) British Standard (Fire Test) 476 part 4 / part 6 / part 7MTEC (Corrosion Rate Test)
 
Fire Safety
Contains no combustible materials, Smoke & Toxic Gas, according to British tests.
 
Standard Test
British Standard(Fire Test) Bs 476 part 4,6,7
 
Wood core
sheet style
It is High Density Particle Board which can prevent moisture and heat. Made from standard materials from the factory to paint the finished floor especially. There are standard sizes, width x length 600 x 600 mm., thickness 28 mm. (depending on the surface of the slab) with a steel sheet (EG) of 0.60 mm. thickness, which has anti-rust properties covering the slab around. In the case that the top surface of the slab is covered with High Pressure Laminated (HPL), the slab has a density of not less than 1,000 kg/m3.
 
Sheet size
600x 600 x 31 mm.
 
surface material
High Pressure Laminated ( HPL -Floor grade , Anti Static , Bare )
 
raised floor height
Standard 10 - 60 cm or more than 60 cm
 
lifting weight of the floor
Concentrated Load not less than 500 kg/point
Distributor Load not less than 1,250 kg/square meter
 
test standard
TIS 1129 - 2535 (1992), a set of raised floors that determine the surface electrical resistance
British Standard(Fire Test) Bs 476 part 4,6,7
 
Fire Safety
Contains no combustible materials, Smoke & Toxic Gas, according to British tests.
 
Standard Test
Die cast Aluminum access floor
 
sheet style
Raised floor panels made of Die cast Aluminum panel are used in a variety of applications such as clean room, Lab, semi-conductor work shop and operation room in hospital because of its high strength, good weight distribution and good electrical conductivity. Made from standard materials from the manufacturer of floor slabs. The top is covered with High Pressure Laminated(HPL), PVC (PVC), Ceramic (Ceramic) or Conductive tile etc;
 
Sheet size
600x 600 mm. thickness. 32 ,50 and 52 mm
 
surface material
High Pressure Laminated ( HPL -Floor grade , Anti Static , Bare )
 
raised floor height
Standard 10 - 60 centimeters or more than 60 centimeters according to customer requirements
 
lifting weight of the floor
test standard
TIS 1129 - 2535 (1992), a set of raised floors that determine the surface resistance value
British Standard(Fire Test) Bs 476 part 4,6,7
Fire Safety
Contains no combustibles, Smoke & Toxic Gas, according to the British Standard Test.
British Standard(Fire Test) Bs 476 part 4,6,7
 
Calcium Sulfate access floor
sheet style
The raised floor slabs are made of high strength Calcium sulfate Board material that can prevent moisture and heat from the standard material from the slab manufacturer. The top is covered with High Pressure Laminated (HPL), PVC (PVC), Ceramic (Ceramic) etc; The bottom is covered with aluminum foil (Aluminum foil) or galvanized steel sheet (Galvanize steel sheet). The four sides are covered with black PVC (Black PVC).
 
Sheet size
600x 600 mm. thickness. 28 ,32 and 37 mm
 
surface material
High Pressure Laminated (HPL -Floor grade , Anti Static , Bare)
 
raised floor height
Standard 10 - 60 centimeters or more than 60 centimeters according to customer requirements
 
lifting weight of the floor
Fire Safety
Contains no combustible materials, Smoke & Toxic Gas, according to British tests.
Standard Test
British Standard(Fire Test) Bs 476 part 4,6,7
Ventilated floor panel , Import
 
sheet style
Ventilated floor ( Perforated panel ) structure made of steel coated with Epoxy Powder Coating to prevent rust and static electricity. top surface and the bottom is drilled so that the air below can breathable And can install panels to adjust the ventilation rate under (Damper) ventilation rate from 20%-45% on the surface of HPL, PVC .Conductive tile….etc.
Sheet size
600x 600 mm.
 
surface material
High Pressure Laminated ( HPL - Floor grade , Anti Static)
 
raised floor height
Standard 10 - 60 centimeters or more than 60 centimeters according to customer requirements
 
lifting weight of the floor
Download
Fire Safety
Contains no combustibles, Smoke & Toxic Gas, according to the British Standard Test.
British Standard(Fire Test) Bs 476 part 4,6,7
Laminated flooring , Import
 
feature
The surface is scratch resistant. The surface does not make it slip. There are many colors to choose from. according to personal preference Able to withstand a certain degree of heat, chemical resistant and non-flammable, the floor does not collect dust and germs unlike carpets and tiles, and is easy to clean. Suitable for indoor use, residential, shops, meeting rooms, however, the strength model should be selected appropriately.